Inline Detonation KITO Armaturen - Bi-directional in-line detonation flame arrester, short-time burning proof - G 26.2.1 N
Inline Detonation KITO Armaturen - Bi-directional in-line detonation flame arrester, short-time burning proof - G 26.2.1 N

KITO Armaturen - Bi-directional in-line detonation flame arrester, short-time burning proof - G 26.2.1 N

KITO® deflagration flame arrester

If potentially explosive gas-air mixtures ignite in a section of pipeline, the explosion starts out as a deflagration propagating at relatively low pressures and flame speed below speed of sound.

Standard (Options)
  • DIN
Connection (Options)
  • Flanged
Material (Options)
  • 1.4571
  • Steel
Pressure Rating (Options)
  • PN 40
 

KITO® RG-Det4-IIA-…-4.5

KITO® RG-Det4-IIA-…-4.5-T (-TT)

– design with flange connection-

  • For installation into pipes to the protection of vessels and components against stable detonation of flammable liquids and gases.
  • Tested and approved as detonation flame arrester type 4.
  • Approved for all substances of explosion groups IIA1 to IIA with a maximum experimental safe gap (MESG) > 0.9 mm.
  • Bi-directionally working in pipes, whereby an operating pressure of 4.5 bar abs. and an operating temperature of 60 °C must not be exceeded.
  • All sizes are tested against “stabilized burning” and withstand this up to a max. burn time BT ≤ 1.0 min.
  • To detect a “stabilized burning” a temperature sensor must be installed at each endangered side.
  • Mounting is acceptable in any position, in horizontal as well as in vertical pipes.
KITO Armaturen - Bi-directional in-line detonation flame arrester, short-time burning proof - G 26.2.1 N